Construction of Class
B0, B15, A15, A30, & A60
Construction details
of A Class decks of A15 Class ceilings of A60, A30, or A15
standard, or of B Class ceilings of B0 and B15 standards to comply
with the requirements of :
 |
The amendment to the International Convention
For The Safety Of Life At Sea 1974 (ratified on
20/11/1981) Chapter 2.2: Part A: Regulations 3.3 &
3.4.
|
|
 |
| The Merchant Shipping (Fire Protection)
Regulations 1984: Part 1: Regulation 1(2). |
|
 |
| The Fishing Vessels (Safety Provisions) Rules
1975: Part 1: Rule 1(5). |
|
Ceiling boards may be faced on both sides
with material having a Class 1 surface
spread of flame rating when tested in
accordance with the criteria of BS 476: Part
7: 1987.
Cover fillets of
PROMARINE®-640
board, minimum 12.7mm thick, must be
inserted between ceiling panels and top
supporting channels. When the ceiling panels
are specified as A60 standard, essential
mineral wool insulation is 50mm thick and
fitted to the deckhead.